Description
06DM8086GC3650
06DM = Service Compressor - Replacement for new 06DA, DM without unloading
8 = Motor Size
08 = Displacement in CFM at 1750 RPM
6 = Service Compressor, Remanufactured
G = Pump End Suction Service Valve, Plain, 225D
C = With Internal Thermostat and Without External Overloads
36 = 400/460-3 (50/60)
5 = No Oil
0 = Single Pack Base Unit Unpackages
06DM = Service Compressor - Replacement for new 06DA, DM without unloading
8 = Motor Size
08 = Displacement in CFM at 1750 RPM
6 = Service Compressor, Remanufactured
G = Pump End Suction Service Valve, Plain, 225D
C = With Internal Thermostat and Without External Overloads
36 = 400/460-3 (50/60)
5 = No Oil
0 = Single Pack Base Unit Unpackages
Standard Features
- High-flow, automatically reversible oil pump provides positive-displacement oil lubrication.
- Crankcase venting system equalizes pressure during startup and assures oil return to sump.
- Oversize sump holds extra oil in crankcase to prevent levels dropping below safe lubrication range during flooded starts.
- Contoured pistons lower cylinder clearances to increase compressor capacity and efficiency.
- High-efficiency valves provide increased refrigerant flow and lower pressure drops.
- Electronic oil-pressure switch.
Specifications
- BrandCarlyle
- ApplicationMedium Temperature, Refrigeration Duty
- CFM Displacement08
- Cylinders2
- DesignRemanufactured Service
- HP3
- RefrigerantR134A, R22, R404A, R407A, R407C, R407F, R448A, R449A, R450A, R452A, R500, R502, R507, R513A
- Suction Line Size7/8"
- Variety Type06D/6D - Reciprocating
- Voltage400/460
- Capacity (Air Cooled)36.5 btu
- Capacity (Water Cooled)39.9 btu
- Frequency50Hz, 60Hz
- LRA35.5
- Max RLA7/5.6
- Max Watts3,400/4,100
- Motor Phase3
- MTA8.7
- Oil Charge3 pints
- SC0 °F
- SCT (Air Cooled)130 °F
- Shipping Height24 in
- Shipping Length25 in
- Shipping Point37406
- Shipping Weight194 lb
- Shipping Width20 in
- SST (Air Cooled)45 °F
- SST (Water Cooled)40 °F
- Suction Temperature Range0 - 50